Descripción
Estándares
Internacional : HD 308 S2; IEC 60092-353; IEC 60332-3 Cat.A; IEC 60754-1Descripción
Approval certificates
Adapted to VDE 0295
Application
In dry and moist rooms and outdoor use for light mechanical stresses. Not for direct burial and not in water. As supply or interconnecting cable for measuring, controlling regulating and power supply. For control and power equipment on conveyors and production lines and for regulating and monitoring work processes in industrial plants and production lines. For flexible use with light mechanical stress, free motion without periodic recurrence and without forced guidance. Especial for the use in public areas and buildings where special requirements regarding fire protection and security are requested.
Design
- Conductor
Copper bare stranded, Class 5 according to DIN VDE 0295:1995-06 or
IEC 60228
- Insulation
special XLPE compound Type HF according to IEC 60092-351
- Outer sheath
Halogen free compound complying with SHF1 according to IEC 60092-359
and HM4 according to VDE 207 part 24
- Core identification
According to DIN VDE 0293:1990-01
JB/OB: coloured cores according HD 308 S2 with/or without green/yellow core
JZ/OZ: black, white printed N° 1,2,... and with/ or without green/yellow core
- Core colours
2 cores: blue + brown
3 cores: blue + brown + green/yellow
4 cores: grey + brown + black + green/yellow
5 cores: blue + brown + black + grey + green/yellow
- Packaging
on request
Características
Características de la construcción | |
---|---|
Halogen free | IEC 60754-1 |
Conductor flexibility | Flexible class 5 |
Material del conductor | Bare copper |
Lead free | Sí |
Meterial de la capa externa | HFFR (Halogene Free Flame Retardant) |
Aislamiento | XLPE (Cross-linked Polyethylene) |
Características eléctricas | |
Insulation resistance at 20°C | 50.0MOhm.km |
Tención | 0,6 / 1 kV |
max.peak voltage (num) | 1,7kV |
Maximum operating voltage | 1,2kV |
Test voltage | 4000V |
Características mecánicas | |
Resistencia mecánica a impactos | Normal industrial use |
Flexibilidad del cable | Flexible |
Características de uso | |
Resistencia a radiación ultravioleta | Sí |
Densidad de humo | IEC 61034 |
Retardación a fuego | IEC 60332-3 Cat. A |
Emisión de gases corrosivos | IEC 60754-2 |
Emisión de gases tóxicos | No toxicity to IEC 60754-1 |
Factor dinámico de curvatura | 15(xD) |
Faja de temperatura operacional (Min .. Máx) | -5 .. 90°C |
Temperatura máxima del conductor en servicio continuo | 90°C |
Ambient static operating temperature, range | -35 .. 90°C |
Ozone resistance | Yes |
RoHS compliant | Yes |
Silicone free | Yes |
Bending factor when installed | D>25mm: 6 (xD); D<25mm: 4 (xD) |
Oil resistance | Yes |
Specific characteristics | |
See all products | |
|
Products and services
Información relacionada
Vender información de entrega
Marking
- NEXANS RHEYFLEX POWER XH-JB 0,6/1 kV n G s HFFR IEC 60332-3 Cat. A CE RoHS conform YYYY FA-Nr MMMM MADE IN GERMANY
- NEXANS RHEYFLEX POWER XH-OB 0,6/1 kV n x s HFFR IEC 60332-3 Cat. A CE RoHS conform YYYY FA-Nr MMMM MADE IN GERMANY
- NEXANS RHEYFLEX POWER XH-OZ 0,6/1 kV n x s HFFR IEC 60332-3 Cat. A CE RoHS conform YYYY FA-Nr MMMM MADE IN GERMANY
- NEXANS RHEYFLEX POWER XH-JZ 0,6/1 kV n G s HFFR IEC 60332-3 Cat. A CE RoHS conform YYYY FA-Nr MMMM MADE IN GERMANY
FA-Nr = Production lot
MMMM = Meter marking