Afitox SM BMCS 150/250 (300)V (With additional communication pair)
Description
Application
For fixed installations in all areas, where the circuit integrity is essential.
Description
For fixed installations in all areas, where the circuit integrity is essential.
Standards
International : IEC 60092-350; IEC 60092-351; IEC 60092-359; IEC 60092-376; IEC 60331; IEC 60332-1; IEC 60332-3-22 Cat.A; IEC 60754-1; IEC 60754-2; IEC 61034-1/2Description
Construction
- Conductor: stranged annealed tinned copper wires class 2; IEC 60228; each core made up of 7 stranded copper wires;
- Thermal Barrier: layer of mica tape;
- Insulation: HF XLPE halogen free crosslinked polyethylene;
- Separator: polyester tape;
- Shield: overall aluminium/polyester tape (0,065mm thick) with stranded tinned copper drain conductor 0,5m² (7 wires);
- Bedding: extruded polyolefin halogen free compound;
- Armour: galvanized steel wire braid;
- Outer Sheath: grey thermoplastic polyolefin halogen free compound (SHF1). Orange for telecom cables (UV protected) and blue for instrinsically safe areas application. Marked with red strip.
Additional Communication Pair: all multi-core have an additional communication pair orange and blue coloured.
Identification of Cores:
pair - black and white coloured insulation; each pair with printed numbers;
triad - black, white and green coloured insulation; each triad with printed numbers;
quad - black, white, green and red coloured insulation (technical information can be request).
Assembly of Cores: twisted pairs, triads or quads (cabled with fillers where necesary to make round).
Routine Tests:
- electrical resistance of conductor;
- electric voltage;
- insulation resistance referred to 20°C.
Packing: wood reels in accordance with the terms of NBR 11137.
Tolerance: thickness and dimensions are considered as nominal values, subject to industry tolerance.
Minimum Bending Radius: values according to nominal outside diameter. During installation, must be used eight times the measured diameter.
This product is part of our Shiplink® offer.
Characteristics
Construction characteristics | |
---|---|
Conductor shape | RN |
Dimensional characteristics | |
Number of round wires | 7 |
Usage characteristics | |
Max. conductor temperature in service | 90°C |
Short-circuit max. conductor temperature | 250°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Selling information
T: Triad
RN: Non Compacted Round Stranded