For inside and outside use in railway vehicles (locomotives, trains, trolley-busses, etc.), switching stations and control panels. Installation in cable ducts, tubes and outside.
For wiring in switching stations and distribution boards up to 1000 V, this cable is short-circuit and earth fault save.
Current-carrying capacity acc. to EN 50343 as well as VDE 0298 part 4.
Serves request with regard to Hazard Level 4 acc. to EN 45545-1
1. Conductor
Flexible stranded tinned copper, acc. to DIN VDE 0295/IEC 60228/HD 383 class 5,
conductor wrapping optional
2. Insulation
Special cross-linked EPR, rubber type EI 110 acc. to EN 50264-1
3. Outer sheath
Special cross-linked EVA, rubber type EM 104 acc. to EN 50264-1,
oil-, diesel-oil, ozone- and uv- resistant
Ink-marking white on black core
RHEYHALON VDE-Reg.-Nr. 7905 ; NSHXAFOE EN 1.8/3 kV
EN 50264-3-1 1800V 2.5 OM ; FA-Nr. ....
Black (BK)
DIN 5510 part 1 Flame protection class 1, 2, 3 and 4
BS 6853
Nominal voltage
Uo/U (Umax) = 1,8/3 (3,6) kV
Max. operating voltage (d.c.)
Vo =2,7 kV
Testing a.c. voltage (5 minutes)
U = 6,5 kV
Conductor at normal operation
≤ 90 °C/250.000 h
≤ 120 °C/20.000 h
Overload
≤ 160 °C / 50 h
Conductor under short-circuit conditions (tinned)
≤ 200 °C
Other cross-sections on request.
Special conditions relating temperature and bending radii (e.g. by compelled guidance into cluthes, wagon transition and boogies) on request.